NDFA Series Fully Automatic Variable-Frequency Transformer Comprehensive Tester
Contact phone number:
Product Center
-
Series Resonant Withstand Voltage Test Device
-
High-Voltage Withstand Voltage Test Equipment Series
-
Transformer Testing Series
-
Insulating Oil and SF6 Gas Testing Equipment
-
Insulation Resistance and Grounding Resistance Testing Series
-
Instrument transformer, relay, and pressure relief valve testing series
-
Switchgear, Circuit Breaker, and Surge Arrester Testing Series
-
Battery and DC System Testing Series
-
Generator and Motor Testing Series
-
Cable and Overhead Line Inspection Series
-
Secondary Protection Testing Series
-
Partial Discharge-Free Detection and Live On-Line Monitoring Series
-
Power Quality and Safety Tools Testing Series
-
Other
Product Details
■ Key Features
Simply set the basic parameters: specify the current transformer’s rated values. The instrument automatically records data throughout the entire test, and it also calculates and displays the turns ratio and polarity, as well as the volt‑ampere characteristic curve, eliminating the tedious tasks of rewiring, manual voltage adjustment, manual data recording, data compilation, and curve plotting.
On-site verification of current transformers requires no standard current transformer, current booster, burden box, voltage regulator control box, or high‑current conductors. With extremely simple test wiring and operation, the verification process is streamlined, significantly reducing labor intensity and enhancing efficiency, thereby facilitating convenient on-site testing of current transformers. Fast, simple, precise, and convenient.
-------------------=Comprehensive Features=-----------------
★ It not only meets the testing requirements for the excitation characteristics (i.e., volt‑ampere characteristics), turns ratio, polarity, secondary winding resistance, secondary burden, ratio error, and phase angle error of various CTs—including protection, metering, and TP types—but can also be used to test the excitation characteristics, turns ratio, polarity, and secondary winding resistance of various PT electromagnetic units.
★ Automatically provides CT parameters such as the inflection-point voltage/current, 10% (5%) error curves, accuracy limit factor (ALF), instrument security factor (FS), secondary time constant (Ts), remanence coefficient (Kr), and both saturated and unsaturated inductances.
★ The tester complies with various instrument transformer standards, including GB 1208 (IEC 60044‑1), GB 16847 (IEC 60044‑6), and GB 1207, and automatically selects the appropriate standard for testing based on the type and class of the instrument transformer.
★ Based on advanced low-frequency testing principles, it can handle CT tests with a knee point voltage exceeding 40 kV.
★ The testing is simple and convenient, allowing you to complete CT DC resistance, excitation, turns-ratio, and polarity tests with a single button. Moreover, except for the load test, all other CT tests use the same wiring configuration.
★ 10-inch color large-screen, fully Chinese‑localized graphical interface; user‑friendly and aesthetically pleasing; all‑Chinese graphical display; built-in panel printer for on‑demand printing of trend charts and test data.
★ Equipped with a large-capacity memory, it can store 2,000 sets of test data, with data retention that is non-volatile and never lost upon power failure.
★ After the test is completed, the data is saved to a USB flash drive, allowing for data analysis on a computer using dedicated software and the generation of a Word‑format report.
★ Automatic inflection-point calculation, test-data filtering and printing, and built-in date/time functionality.
★ All-in-one standalone unit, lightweight at just 8 kg, easy to carry and ideal for mobile testing.
■ Technical Specifications
For testing purposes | Protection and metering CTs, protection PTs | |
Input power supply | Voltage | AC 220V ±10% |
Frequency | 50/60Hz | |
Output | Voltage | 0~180Vrms |
Electric current | Maximum 12 Arms, 36 A (peak) | |
CT ratio Measurement | Scope | 1~40000 |
Accuracy | ±0.2% | |
PT transformation ratio Measurement | Scope | 1~40000 |
Accuracy | ±0.5% | |
Phase measurement | Accuracy | ±3 minutes |
Resolution | 0.3min | |
Secondary Winding Resistance Measurement | Scope | 0~300Ω |
Resolution | 1 mΩ | |
Accuracy | 3% ± 1 mΩ | |
AC Load Measurement | Scope | 0~1000VA |
Resolution | 0.01VA | |
Accuracy | 0.2%±0.1VA | |
Environmental conditions | Operating temperature | -10℃ to +50℃ |
Storage temperature | -10℃ to +50℃ | |
Humidity | Relative humidity: 5%–95%, non-condensing | |
Instrument dimensions | 340mm×296mm×174mm | |
Instrument weight | Weight < 8 kg | |
Service system
Offering inspection and reception services
We guarantee to welcome your visit at any time and provide you with every possible convenience.
Provide a reasonable quotation.
We guarantee to provide a unified, reasonable quotation for the products you request within 24 hours.
Provide professional technical support
We guarantee that a technical specialist will respond to any technical questions you may have within 24 hours.
Provide detailed information
We guarantee that, within 24 hours, the product catalogues, software CDs, and other technical materials you require will be delivered to your company by our local branch or office.
Related products
Power Technology
2016-04-05
Leave a message for inquiry
Contact Us
National Service Hotline: 400-027-8938
Mobile (Manager Chen): 133 9714 9829
Address: Building No. 5, Donghu High-tech Industrial Innovation Base, No. 9 Miaoshan Avenue, Miaoshan Development Zone, Jiangxia District, Wuhan City
Scan it
Follow the official mobile website