Performance Features

1. Strong anti-interference capability: The device’s resistance to electric-field-induced interference reaches 2 mA (50 Hz), and it is capable of measuring the insulation resistance of large 500-kV transformers on-site at a 500-kV substation without disconnecting the leads.

2. Large short-circuit current : The typical short-circuit current is 10 mA, making it suitable for testing high-capacity and high-inductance devices.

3. Wide resistance measurement range: The measurement range starts from 0.01 MΩ. ~1999 GΩ , accurate readings and high resolution.

4. Wide high-voltage output range: Options include 0.1 kV, 0.25 kV, 0.5 kV, 1 kV, 2.5 kV, and 5 kV; voltage can also be smoothly adjusted from 0 V to the desired level.

5. Audio-visual alerts: It features a timing function to remind users to record and analyze the absorption ratio and polarization index of the measured object.

6. High Quality: All critical components are sourced from imported parts, ensuring accurate measurement precision.

7. Ease of Use: It features an all-in-one chassis, offering a compact footprint, lightweight design, and easy portability.

8. Exquisite appearance: Made from robust, highly wear-resistant materials, the instrument boasts a premium feel and an extended service life.

Technical indicators

1. Test voltage levels: 0.1 kV, 0.25 kV, 0.5 kV, 1 kV, 2.5 kV, 5 kV

2. Test voltage accuracy: ±(5% + 10 V)

3. Short-circuit current: typical value 10 mA

4. Range and Accuracy

Quantity    Cheng

Effective range for resistance measurement

Refined    degree

20 MΩ

0.01–19.99 MΩ

±(5%+3d)

200 MΩ

5.0–199.9 MΩ

±(5%+3d)

2 GΩ

0.05~1.999 GΩ

±(5%+3d)

20 GΩ

0.5–19.99 GΩ

±(5%+3d)

200 GΩ

5.0–199.9 GΩ

±(10% + 3d)

2000 GΩ

50–1999 GΩ

±(20%+10d)

5. Immunity to electric field interference: 2 mA (50/60 Hz).

6. Time‑keeping and alarm functions: The stopwatch displays a maximum of 19 minutes and 59 seconds, cycling every 20 minutes; audible alerts sound at 15 seconds, 60 seconds, and each minute. Upon reaching the set time, a brief beep is emitted, and the resistance reading remains displayed for 3 seconds. If the measured resistance falls below the lower range limit or the reading is invalid, a continuous audible alarm is activated.

7. Display panel: Three 3½-digit LCD displays, showing the test voltage, resistance, and time, respectively.

8. Power Supply: Includes ten 1.2 V/2000 mAh Ni‑MH rechargeable batteries, providing a total of 12 V DC. Equipped with an AC input (50/60 Hz, 220 V) for battery charging or float‑charge operation.

9. Operating Environment

Temperature: -20℃ to +40℃

Relative humidity: 20%–90%

10. Dimensions: 315 × 240 × 180 mm (Length × Width × Height)

11. Weight: 5.5 kg


Service system


Offering inspection and reception services

We guarantee to welcome your visit at any time and provide you with every possible convenience.

Provide a reasonable quotation.

We guarantee to provide a unified, reasonable quotation for the products you request within 24 hours.

Provide professional technical support

We guarantee that a technical specialist will respond to any technical questions you may have within 24 hours.

Provide detailed information

We guarantee that, within 24 hours, the product catalogues, software CDs, and other technical materials you require will be delivered to your company by our local branch or office.

Related products


Power Technology


Leave a message for inquiry


Welcome to leave us an online message; we will get back to you promptly.

%{tishi_zhanwei}%