  • 4b488f57-0faa-433c-a5bb-c9953aa22f89.jpg

NDXB-Y Series AC Withstand Voltage Resonant Test System for Power Cables (Oil-Immersed Type)



Contact phone number:

Product Details


■Product Overview

Used for 10kV35kV110kV For AC withstand voltage testing of cables, the variable-frequency series resonance withstand test utilizes the inductance of a reactor and the capacitance of the device under test to achieve capacitive resonance, thereby generating high voltage and large current across the test specimen. The AC withstand voltage test system for cables primarily consists of a variable-frequency power supply. ( Host ) It consists of an excitation transformer, a reactor, and a capacitive voltage divider.

The frequency adjustment range is 30~300Hz , in compliance with the enterprise standards issued by China Southern Power Grid Company ( The “Regulations for Preventive Testing of Power Equipment” can not only meet the requirements of high-voltage… XLPE It meets the voltage withstand requirements for cables and is lightweight. ( The weight of a single component shall not exceed 30kg) Its excellent portability makes it well suited for field testing.

 

Common Configuration Table for Variable-Frequency Resonance in AC Withstand Voltage Testing of Cables

35kV Configuration Table for Withstand Voltage Testing Equipment for Cables of 1 kV and Below

Model Name

Control box

Reactor

Excitation transformer

Voltage divider

Scope of Application

NDXB-F -   44/22

2.5kW

1A/22kV Two units

2.5KVA/1kV

25kV

10kV Cable ≤1km

ND  XB-F-  88/22

4kW

2A/22kV Two units

4KVA/1kV

25kV

10kV Cable ≤2km

NDXB-F -   132/22

6kW

2A/22kV Three units

6KVA/1/3kV

60kV

10kV Cable ≤3km

35kV Cable ≤1km

NDXB-F -   176/22

7.5kW

2A/22kV Four units

7.5KVA/3kV

60kV

10kV Cable ≤4km

35kV Cable ≤1km

NDXB-F -   264/22

10kW

2A/22kV Six units

10KVA/1/3kV

60kV

10kV Cable ≤6km

35kV Cable ≤2km

NDXB-F -   330/22

15kW

2.5A/22kV Six units

15KVA/1kV

100kV

10kV Cable ≤8km

35kV Cable ≤2km

NDXB-F -   640/22

25kW

2A/22kV Eight units

25KVA/1/3/5kV

200kV

10kV Cable ≤10km

35kV Cable ≤4km

110kV Cable ≤1km

 

110kV Configuration Table for Withstand Voltage Testing Equipment for Cables of 1 kV and Below

Model Name

Control box

Reactor

Excitation transformer

Voltage divider

Scope of Application

NDXB-F- 1300/130

50kW

5A/130kV Two units

505KVA/1/3/5kV

150kV

35kV Cable ≤2km

110kV Cable ≤2km

NDXB-F- 260/130

100kW

5A/130kV Four units

100KVA/1/3/5/10kV

220kV

35kV Cable ≤3km

110kV Cable ≤3km

220kV Cable ≤1.5km

NDXB-F- 3200/220

160kW

4A/220kV Four units

160KVA/5/10kV

220kV

110kV Cable ≤5km

220kV Cable ≤3km

NDXB-F-6400/220

320kW

8A/220kV Four units

320KVA/5/10kV

320kV

110kV Cable ≤10km

220kV Cable ≤5km

500kV Cable ≤1km

 

■ Product Specifications

Rated output voltage

0~220kV

Output frequency

30~300Hz

Resonant voltage waveform

Pure sine wave, waveform distortion rate ≤ 1.0%

Full-load operating time

Continuous working hours 60min

Quality factor

30~90

Frequency adjustment sensitivity

0.1Hz

Instability degree

<0.05%

Power supply

Single-phase 220V or three-phase 380V ± 15% , power frequency 50Hz ± 5%

 

■Product Features

Easy to operate : Automatic tuning ( Automatic resonance point search ) , Automatic Testing ( Automatic resonance point tracking and automatic voltage boosting ) and manual testing ( Manually searching for the resonance point and manually boosting the voltage ) The three modes cater to different test requirements. They allow adjustment of the test voltage, frequency‑modulation range, protection current, and pressurization time.

Automatic mode : Simply set the test voltage and duration; the equipment automatically and precisely adjusts frequency and voltage, completes the test, and saves the data.

It features ground fault and flashover protection.

It can automatically track changes in grid voltage and adjust the voltage in real time, ensuring stable high-voltage levels.

Easy to operate ; Single-phase 220V Or three-phase 380V The power supply is universal, making on-site power access convenient.

Reactors of the same voltage level and capacity are smaller in size and lighter in weight. ; The temperature rise is small under rated load. ; Adopting dry-type epoxy casting , High mechanical strength and excellent electrical insulation properties. , Beautiful and can be concealed.

Flexible configuration : The reactor can be connected in series. / It can be used in parallel to meet the requirements of various test specimens, enabling multi‑purpose operation with high cost‑effectiveness.


Service system


Offering inspection and reception services

We guarantee to welcome your visit at any time and provide you with every possible convenience.

Provide a reasonable quotation.

We guarantee to provide a unified, reasonable quotation for the products you request within 24 hours.

Provide professional technical support

We guarantee that a technical specialist will respond to any technical questions you may have within 24 hours.

Provide detailed information

We guarantee that, within 24 hours, the product catalogues, software CDs, and other technical materials you require will be delivered to your company by our local branch or office.

Related products


Power Technology


Leave a message for inquiry


Welcome to leave us an online message; we will get back to you promptly.

%{tishi_zhanwei}%