Product Details


1

The 35 kV insulating rod withstand voltage test stand is developed in accordance with the requirements of DL/T 976-2005, “Preventive Test Procedures for Live Working Tools, Devices, and Equipment,” a power industry standard issued by the National Development and Reform Commission of the People’s Republic of China. This product features lightweight construction and high strength. Its test electrodes are made of 304 stainless steel combined with conductive cotton, ensuring full contact between the electrode and the specimen; all performance parameters meet national standards. It can be used to conduct insulation withstand voltage tests on insulating rods as specified in the “Preventive Test Procedures for Electrical Safety Tools and Equipment.” The product is suitable for all industries related to the power sector.

II. Main Technical Specifications

Voltage level

10 kV

35KV

110KV

Ambient temperature

-10℃ to 40℃

-10℃ to 40℃

-10℃ to 40℃

Humidity

≤90%RH

≤90%RH

≤90%RH

Continuous operating time

Can be continuous

Can be continuous

Can be continuous

Test station

10

10

10

Bracket dimensions

900×350×750mm

900×350×1300mm

900×350×2200mm

Maximum withstand voltage

100KV

150KV

250KV

Weight (kg)

18

22

31

Device Connection Operation

1. Requirements for the test site:

For electroscopes applicable to a specified voltage range, the test shall be conducted in a laboratory shielded against external electromagnetic interference, corresponding to the maximum rated voltage U; when U… N The clearance for voltages ≤35 kV is 1 m, when U N >35 kV, with a spatial range of 2 m or more.

During the test, the contact electrode of the electroscope is brought into contact with the test electrode, and the indicator is positioned approximately on the central axis (horizontal axis) of the annular electrode.

The horizontal distance between the centerline of the test electrode and the annular electrode is shown in Table 3.

Table 3: Electrode Spacing (Horizontal Distance)

U N KV

acmm

aomm

U N KV

acmm

aomm

10

100

300

63—110

650

1000

35

430

300

220—330

850

1000

Note: 1. ac denotes a voltmeter equipped with an extended contact electrode (commonly used in substations), and refers to the distance between the test electrode and the ring-shaped electrode.

2. The AO is a voltmeter without an extended contact electrode (commonly used for power lines); it measures the distance between the test electrode and the ring electrode.

Gradually increase the voltage on the test electrode; when the “voltage present” indicator signals, the starting voltage is measured. If the measured starting voltage falls within the specified range for one of the four types listed below, the test is considered to have passed.


Service system


Offering inspection and reception services

We guarantee to welcome your visit at any time and provide you with every possible convenience.

Provide a reasonable quotation.

We guarantee to provide a unified, reasonable quotation for the products you request within 24 hours.

Provide professional technical support

We guarantee that a technical specialist will respond to any technical questions you may have within 24 hours.

Provide detailed information

We guarantee that, within 24 hours, the product catalogues, software CDs, and other technical materials you require will be delivered to your company by our local branch or office.