Technical indicators
1. Input Characteristics
Voltage measurement range: 0–500 V, with automatic range switching.
Current measurement range: Clamp-on current transformers (three types): 5 A / 25 A (standard configuration)
100A/500A (optional)
1000A/2000A (optional)
Phase angle measurement range: 0~359.99°.
Frequency measurement range: 45–65 Hz.
Number of voltage channels: Three channels (U A , U B , U C ).
Number of current channels: Three channels (I A , I B , I C ).
Maximum harmonic analysis order: 63.
Maximum continuous storage period at 1-minute intervals: 18 months.
2. Accuracy
Electrical Parameter Measurement Section:
Voltage: ±0.2%
Frequency: ±0.01 Hz
Current, Power: ±0.5%
Phase: ±0.2°
Power Quality Section:
Fundamental voltage permissible error ≤ 0.5% F.S.
Fundamental current permissible error: ≤1% F.S.
Measurement error of the phase difference between fundamental voltage and current: ≤0.2°
Harmonic voltage distortion measurement error: ≤0.1%
Harmonic current content measurement error: ≤0.2%
Three-phase voltage unbalance error: ≤0.2%
Voltage deviation error: ≤0.2%
Voltage variation error: ≤0.2%
3. Operating temperature: -10°C to +40°C
4. Charging power supply: AC 220 V, frequency 45 Hz–55 Hz
5. Host power consumption: ≤3 VA
6. Maximum battery operating time: ≤8 hours
7. Insulation:
1) The insulation resistance between the voltage and current input terminals and the enclosure shall be ≤100 MΩ.
2) The power supply input terminals shall withstand a 1.5 kV (RMS) power-frequency voltage relative to the enclosure for a duration of 1 minute.
8. Dimensions: 320 mm × 240 mm × 130 mm
9. Weight: 2.0 kg
Service system
Offering inspection and reception services
We guarantee to welcome your visit at any time and provide you with every possible convenience.
Provide a reasonable quotation.
We guarantee to provide a unified, reasonable quotation for the products you request within 24 hours.
Provide professional technical support
We guarantee that a technical specialist will respond to any technical questions you may have within 24 hours.
Provide detailed information
We guarantee that, within 24 hours, the product catalogues, software CDs, and other technical materials you require will be delivered to your company by our local branch or office.
Related products
Power Technology
2016-04-05
Leave a message for inquiry
Contact Us
National Service Hotline: 400-027-8938
Mobile (Manager Chen): 133 9714 9829
Address: Building No. 5, Donghu High-tech Industrial Innovation Base, No. 9 Miaoshan Avenue, Miaoshan Development Zone, Jiangxia District, Wuhan City
Scan it
Follow the official mobile website