Product Details


■ Product Overview

DC high-voltage generators are primarily used by the power sector, as well as by industrial and mining enterprises, metallurgical plants, steel mills, and other organizations with power departments, to perform DC withstand voltage tests or DC leakage current tests on high-voltage electrical equipment such as zinc oxide surge arresters, power cables, transformers, circuit breakers, and generators.

Application of this instrument AIPWM Technology , To PWM The instrument’s accuracy has been significantly improved by correcting the non‑linearities in its measurement characteristics, and it employs… A1 The technical design incorporates overvoltage and overcurrent protection, addressing the limitations of digital rotary switches that allow only voltage setting while precluding current adjustment and compensating for voltage drift. , While maintaining manual 0.75UDC1mA Based on the function control knob, an additional feature has been added. AI Fully automatic measurement of oxide surge arresters , Cable section withstand voltage test, automatic withstand voltage test function , And it can directly print and save test reports. , It avoids the errors inherent in handwritten lab reports, retains the manual mode, and adds a printing function for arbitrary voltage and current settings. , and total time T1 and split timing T2 Functionality: The instrument now features a perpetual calendar and timekeeping functions, and experimental reports are stamped with the date and time.

■ Technical Features

Fully automatic testing of zinc oxide surge arresters and segmented withstand voltage tests, with display of the voltage rise. / During the voltage‑reduction process, the waiting time is displayed. Voltage and current waveforms are displayed and printed.

Adopt AIPWM Technology, to PWM The inaccuracy of linearity has been corrected, resulting in a significant improvement in accuracy. The ripple factor is ≤ 0.2%

With total time T1 and split timing T2 , as well as printing functionality under any voltage and current conditions.

The instrument has been equipped with a perpetual calendar and time‑keeping functions, and the experimental reports include both the date and time.

■ Product Specifications

Specification

Technical Specifications

60/2

60/5

120/2

120/5

120/10

200/2

200/5

200/10

300/2

300/5

Rated voltage (kV)

60

60

120

120

120

200

200

200

300

300

Rated current (mA)

2

5

2

5

10

2

5

10

2

5

Rated power (W)

120

300

240

600

1200

400

1000

2000

600

1500

Chassis weight (kg)

8

8

2

5

9

405

4.5

5.5

5.5

5.5

Voltage-doubling weight (kg)

4

5

6

8

9

7.0

8.3

9.3

11

11.5

Boost voltage height (mm)

440

440

535

535

750

890

970

980

1250

1250


Service system


Offering inspection and reception services

We guarantee to welcome your visit at any time and provide you with every possible convenience.

Provide a reasonable quotation.

We guarantee to provide a unified, reasonable quotation for the products you request within 24 hours.

Provide professional technical support

We guarantee that a technical specialist will respond to any technical questions you may have within 24 hours.

Provide detailed information

We guarantee that, within 24 hours, the product catalogues, software CDs, and other technical materials you require will be delivered to your company by our local branch or office.

Related products


Power Technology


Leave a message for inquiry


Welcome to leave us an online message; we will get back to you promptly.

%{tishi_zhanwei}%