Product Details
■ Product Features
1. Flexible combination of voltage and current outputs. Output up to 6 Phase voltage 6 Phase current , Can be freely combined to achieve standard functionality. 4 Phase voltage 3 Phase current type, 6 Phase-voltage type, 6 Phase current type, and 12 Phase-type output mode , It is compatible with all conventional testing methods.
2. The standalone operation is convenient. The device’s front panel features a trackball mouse, an optimized keyboard, and a large display. TFT Liquid crystal display , Built-in all Chinese Windows Platform operating software. Ready to use right out of the box. , Easy and quick to operate.
3. Dual operating modes. In addition to standalone operation, the device can also be connected to a laptop or desktop computer for control. , The two methods offer identical functionality, providing a truly comprehensive dual‑operation mode.
Rated parameters
— AC current output
6 Phase current During output Per-phase output (RMS) 0 ~ 3 0A Output precision 0.2 level
3 Phase current During output Per-phase output (RMS) 0 ~ 60A
6 Parallel current output (RMS) 0 ~ 180A
Long-term permissible operating value (RMS) of phase current 10A
Maximum output power of phase current 300VA
6 Maximum output power at maximum current output in parallel connection. 1000VA
6 Permissible operating time at maximum parallel current output 10s
Frequency range (fundamental) 20 ~ 1000 Hz
Harmonic order 1 ~ 20 Next
— Direct current output
Current output 0 ~± 10 A / Each phase Output precision 0.5 level
Maximum Output Load Voltage 20 V
— AC voltage output
Phase voltage output (RMS) 0 ~ 120V Output precision 0.2 level
Line voltage output (RMS) 0 ~ 240V
Phase voltage / Line voltage output power 80VA / 100VA
Frequency Range (Fundamental) 20 ~ 1000 Hz
Harmonic order 1 ~ 20 Next
— DC voltage output
Phase voltage output amplitude 0 ~± 160V Output precision 0.5 level
Line voltage output amplitude 0 ~± 320V
Phase voltage / Line voltage output power 70VA / 140VA
— Digital signal
8 Digital input for the road
Normally open contact 1 ~ 20mA,24V
Potential contact connection “ 0”:0 ~ +6V ; “ 1”: +11 V ~ +250 V
4 For discrete output signals DC :220 V / 0.2 A ; Air conditioning :220 V / 0.5 A
— Time measurement range
0.1 m s ~ 9999s , Measurement Accuracy < 0.1mS
Service system
Offering inspection and reception services
We guarantee to welcome your visit at any time and provide you with every possible convenience.
Provide a reasonable quotation.
We guarantee to provide a unified, reasonable quotation for the products you request within 24 hours.
Provide professional technical support
We guarantee that a technical specialist will respond to any technical questions you may have within 24 hours.
Provide detailed information
We guarantee that, within 24 hours, the product catalogues, software CDs, and other technical materials you require will be delivered to your company by our local branch or office.