At present, China’s distribution network… of the net The neutral point is generally not directly grounded; when a single-phase-to-ground fault occurs on a transmission line, the current flowing through the fault point is, in fact, the capacitive current generated by the line’s capacitance to ground.

The power regulations stipulate that when 10kV and 35kV The system capacitive currents are respectively greater than 30A and 10A At that time, an arc-suppression coil should be installed to compensate for the capacitive current.

In order to verify whether this distribution system will experience PT Resonance and the nature of the resonance that occurs also require accurate measurement of the distribution network’s ground capacitance.

Traditional methods for measuring the capacitive current in distribution networks include the direct method using single-phase metallic grounding and the indirect method employing an external capacitor. However, these approaches require contact with primary equipment, which entails risks during testing, cumbersome procedures, and low operational efficiency.

Fully automatic capacitive current tester, From PT The heterofrequency test signal injected at the open-delta point is directly from PT The secondary side is used to measure the capacitive current in the distribution network. Compared with traditional testing methods, this instrument eliminates the need to interface with the primary side, thereby removing any associated testing hazards. It also obviates the need for cumbersome safety measures and lengthy waits for dispatch instructions; all that is required is to connect the measurement leads to... PT The data on the capacitive current can be measured at the open‑delta terminal.

This method Will not affect relay protection and PT It itself produces no impact and yet avoids it. 50Hz the power-frequency interference signal, while The output terminal of the tester can withstand 100V of the AC voltage; moreover, even if a single-phase-to-ground fault occurs in the system during measurement, it will not cause damage. PT and the testing instrument, so no special safety measures are required, This makes the task safe, simple, and fast, while ensuring that test results are accurate, stable, and reliable.

The tester features a large‑screen LCD with a Chinese menu, offering simple operation. Its compact size and lightweight design make it easy to carry for field work. Wiring is straightforward, testing is fast, and data accuracy is high, significantly reducing the workload of test personnel and boosting operational efficiency.

Technical indicators

1 Measurement range

Total ground capacitance ≤120 microfarads (Three-phase to ground);

Capacitive current ≤ 1400A ( 66kV System)

Capacitive current ≤760 A ( 35kV System)

Capacitive current ≤ 220A ( 10kV System)

Capacitive current ≤130 A ( 6kV System)

2 , measurement accuracy

0.5μ F ~ 1 microfarads ± 10% ±5 characters

1 mu F ~ 90 mu F ±5%

90 mu F ~ 120 mu F±10 %

3 , Environmental conditions: Temperature - 10 ~ 50 °C Humidity ≤90%

4 Power supply :  AC 220V ± 10% 50Hz ± 1%

5 Appearance and weight : 310 ×  300 × 170mm  10 kilogram


Service system


Offering inspection and reception services

We guarantee to welcome your visit at any time and provide you with every possible convenience.

Provide a reasonable quotation.

We guarantee to provide a unified, reasonable quotation for the products you request within 24 hours.

Provide professional technical support

We guarantee that a technical specialist will respond to any technical questions you may have within 24 hours.

Provide detailed information

We guarantee that, within 24 hours, the product catalogues, software CDs, and other technical materials you require will be delivered to your company by our local branch or office.

Related products


Power Technology


Leave a message for inquiry


Welcome to leave us an online message; we will get back to you promptly.

%{tishi_zhanwei}%