产品名称
NDJCY-IV AC sampling and transmitter calibration device
Affiliate classification
Electric meter calibration class
Quantity
-
+
Product description
Product parameters
Features:
● It can check the basic error of various meters in the power system [electric energy meter (option), voltmeter, ammeter, power meter, frequency meter, power factor meter, phase meter], voltage, current, waveform, power factor, etc. The amount of change, etc.;
● The power supply section can generate distortion waves with 2 to 32 harmonics. The number of harmonics, the number of times, the amplitude, and the harmonics can be programmed on the phase of the fundamental wave.
The main parameters:
AC output
|
Voltage limit
|
0~600V
|
Rated voltage range
|
25V、50V、100V、200V、400V、600V
|
|
Current limit
|
0~24A
|
|
Rated current range
|
0.1A、0.5A、1A、5A、10A、20A
|
|
Adjustment range
|
0~120%
|
|
Adjustment fineness
|
5×10-5
|
|
Accuracy
|
Error ≤0.03% (reading) ±0.02% (full scale), Level 0.05
|
|
Output Power
|
100% Fullness, power not less than 20W
|
|
Power
|
Output range
|
Any combination of U×I ranges
|
Accuracy
|
Level 0.05
|
|
Phase output
|
Adjustment range
|
0°~359.99°
|
Resolution
|
0.01°
|
|
Accuracy
|
0.1°
|
|
Power factor
|
Adjustment range
|
-1~0~+1
|
Resolution
|
0.0001
|
|
Accuracy
|
0.05%
|
|
Frequency
|
Adjustment range
|
45Hz~65Hz
|
Resolution
|
0.001Hz
|
|
Accuracy
|
0.01Hz
|
|
Harmonic output
|
Harmonic number
|
2~32次
|
Amplitude
|
0~20%
|
|
Harmonic phase fineness
|
0.01°·N(N is the harmonic order)
|
|
DC output
|
Voltage range
|
75mV, 150mV, 300mV, 3V, 6V, 10V, Output capacity 100mA per gear; 75V, 150V, 300V, 500V, 1000V output capacity 40mA per output
|
Electric flow range
|
30uA, 300uA, 3mA, 30mA Maximum output capacity 9VA; 300mA, 1, 5A, 20A maximum output capacity 10VA;
|
|
Adjustment range
|
0~120% FS
|
|
Adjustment fineness
|
5×10-5
|
|
Accuracy
|
300mV ~ 1000V range error ≤ 0.03% (Reading) ± 0.02% (Fullness): level 0.05, 300uA ~ 1A range error ≤ 0.03% (Reading) ± 0.02% (Fullness): level 0.05
|
|
Dimensions
|
460mm×480mm×200mm
|
|
Weight
|
About 18kg
|