产品名称
ND3020 series electric energy meter field calibrator
Affiliate classification
Electric meter calibration class
Quantity
-
+
Product description
Product parameters
Features:
● The instrument is a high-precision test instrument that integrates energy meter calibration, electrical parameter testing and power quality problems such as waveform distortion, voltage fluctuation and three-phase unbalance in the power grid.
● Accurately measure voltage, current, active power, reactive power, phase angle, power factor, frequency and other electrical parameters to calculate the measurement error of the test equipment loop;
● Display the vector of the measured voltage and current. The user can analyze the vector diagram to get the correctness of the wiring of the measuring device. At the same time, in the three-phase three-wire connection mode, 48 kinds of wiring modes can be automatically judged; the automatic calculation function of the charge-recovery power is convenient for the user to calculate the charge-recovery power for the user who has the problem of wiring;
● Measurement and analysis of the AC power quality supplied by the utility grid to the customer. Measurement and analysis: frequency deviation, voltage deviation, voltage fluctuation, three-phase voltage allowable imbalance and grid harmonics.
Main parameters: calibrator
Input characteristics
|
Voltage measurement range
|
0~400V,57.7V、100V、220V、400V
|
Built-in transformer
|
0~5A
|
|
Phase angle measurement range
|
0~359.999°
|
|
Frequency measurement range
|
45~55Hz
|
|
Precision
|
Voltage
|
±0.05%(±0.1%)
|
Current
|
±0.05%(±0.1%)(Clamp transformer±0.5%)
|
|
Active power
|
±0.05%(±0.1%)(Clamp transformer±0.5%)
|
|
Reactive power
|
±0.3%(±0.5%)(Clamp transformer±1.0%)
|
|
Active energy
|
±0.05%(±0.1%)(Clamp transformer±0.5%)
|
|
Reactive energy
|
±0.3%(±0.5%)(Clamp transformer±1.0%)
|
|
Frequency
|
±0.05%(±0.1%)
|
|
Phase
|
±0.2°
|
|
Fundamental voltage and current amplitude
|
The fundamental voltage tolerance is ≤0.5%F.S.
|
|
The fundamental current error is ≤1%F.S.
|
||
Fundamental phase angle error
|
≤±0.5°
|
|
Harmonic voltage content error
|
≤±0.1%
|
|
Harmonic current content error
|
≤±0.2%
|
|
Three-phase voltage imbalance error
|
≤±0.2%
|
|
Dimensions
|
320mm×240mm×130mm
|
|
Weight
|
About 2kg
|