产品名称
ND-802 Three-phase microcomputer relay protection tester
Affiliate classification
Secondary loop detection class
Quantity
-
+
Product description
Product parameters
Reference standard: DL/T624-1997, JJG1112-2015.
Features:
● With 4-phase voltage 3-phase current output, it is easy to carry out various types of combined output for various types of protection tests. Each phase voltage can output 120V, current three can output 120A, and the fourth phase voltage Ux is a multi-function voltage term, which can be set to 4 kinds of 3U0 or synchronous voltage, or any voltage value output;
● Through the full set of Chinese operating software on the Windows platform, it can perform a variety of large-scale complex and more automated verification work, which can easily test and scan various protection settings, store test data in real time, display vector graphics, Draw fault waveforms, print reports online, etc.
● The ND-802 is a 7-way contact input and a 2-pair empty contact output. The input contact is an empty contact and is compatible with 0~250V potential contacts, which can be intelligently and automatically recognized. Input and output contacts can be expanded according to user needs;
● The device is equipped with a 110V and 220V dedicated adjustable DC power output.
The main parameters:
AC current source
|
Phase current output (Effective value)
|
0~40A
|
|
Triple current output (Effective value)
|
0~120A
|
||
Phase current allowable operating value (Effective value) for a long time
|
10A
|
||
Phase current maximum output power
|
420VA
|
||
Maximum output power at maximum current output
|
900VA
|
||
Allowable working time when triple current maximum output
|
10s
|
||
Output accuracy
|
Level 0.2
|
||
Frequency range (Fundamental)
|
20~1000Hz
|
||
Harmonic number
|
1 to 20 Times
|
||
DC current source
|
Output accuracy
|
Level 0.2
|
|
Current output
|
0 to ±10A / per phase, 0 to ±30A / triple
|
||
Maximum output load voltage
|
20V
|
||
AC voltage source
|
Output accuracy
|
Level 0.2
|
|
Phase voltage output (Effective value)
|
0~120V
|
||
Line voltage output (Effective value)
|
0~240V
|
||
Phase voltage / Line voltage output power
|
80VA / 100VA
|
||
Frequency range (Fundamental)
|
20~1000Hz
|
||
Harmonic number
|
1 to 20 Times
|
||
DC voltage source
|
Output accuracy
|
Level 0.5
|
|
Phase voltage output amplitude
|
0~±160V
|
||
Line voltage output amplitude
|
0~±320V
|
||
Phase voltage / Line voltage output power
|
70VA / 140VA
|
||
Switch input
|
7 Road
|
Empty contact
|
1~20mA,24V
|
Potential contact
|
“0”:0~ +6V; “1”:+11 V~ +250V
|
||
Switch output
|
2 Pairs
|
DC:220V/0.2A;AC:220V/0.5A
|
|
Other
|
Dimensions
|
400mm×300mm×180mm
|
|
Weight
|
About 19kg
|