产品名称
NDFA-V variable frequency transformer integrated tester
Affiliate classification
Transformer detection class
Quantity
-
+
Product description
Product parameters
Reference standard: JB/T5356-2002, JB/T5357-2002.
Features:
● Supports detection of CT and PT (protection, metering class 0.2S, TP class) steady state and instantaneous parameters;
● Adopt advanced DC detection principle, the equivalent excitation voltage is up to 30kV;
● Unique one-button all detection and sub-test detection function, more flexible and convenient on-site use;
● Automatically give the inflection point value according to the procedure;
● Automatically give 5% and 10% error curves.
The main parameters:
Device output
|
0~100Vrms,5Arms(20A Peak)
|
|
Equivalent excitation voltage
|
30kV
|
|
Excitation measurement accuracy
|
≤0.5% (0.2%* Reading +0.3%* Range)
|
|
Secondary resistance
|
Range/Precision
|
0.1~300Ω / ≤0.5%(0.2%*Reading+0.3%*Range)
|
Secondary load
|
Range/Precision
|
5VA~1000VA / ≤0.5%(0.2%*Reading+0.3%*Range)
|
Phase measurement
|
Precision / Resolution
|
±4min/0.1min
|
Ratio difference measurement
|
Range/Precision
|
1-10000 / ≤0.05%
|
PT ratio
|
Range/Precision
|
1-10000 / ≤0.5%
|
CT ratio
|
Range/Precision
|
1-50000 / ≤0.5%
|
Working power
|
AC220V±10% /50Hz
|
|
Dimensions
|
410mm×250mm×300mm
|
|
Weight
|
About 8Kg
|