Copyright:Wuhan Southstar Electric Power Technology Co., Ltd. 鄂ICP备06008607号 Website:300.cn Wuhan
Back to top
Chuangzhi Tiandi, No.13 Yangqiaohu
Avenue, Zanglong Island, Wuhan
Nanxing Power APP
Mailbox:whnx999@126.com
Telephone:400-027-8938
Southstar Electric Power Technology Co., Ltd.
About us
Sales service
News
Recruitment
Contact us
Product display
Wuhan Southstar Electric Power Technology
Co., Ltd. I sincerely look forward to Work
hard with you to create a better future!
Page view:
产品名称
NDBRY-II Transformer low voltage impedance short circuit tester
Affiliate classification
Transformer detection class
Quantity
-
+
Product description
Product parameters
Reference standard: DL/T1093-2008, DL/T1093-2008.
Features:
● With adjustable power supply output, the instrument can complete the measurement of all windings with only one connection;
● Adopting single-phase measurement mode, the short-circuit impedance, reactance and inductance value of each phase can be automatically calculated for the three-phase transformer three-step boosting process;
● Internal phase-locked loop technology is used to simultaneously sample AC signals and measure data accurately;
● Can measure voltage, current, power, frequency, etc.;
● The single-machine measurement voltage and current range are wide, and the external CT and PT are supported to further expand the measurement range.
The main parameters:
Voltage measurement range
|
AC3V~500V
|
Current measurement range
|
AC0.5A~50A
|
Current and voltage accuracy
|
±0.2%
|
Measuring power
|
0.1≤cosΦ≤±0.5
|
Measuring frequency
|
50±2Hz
|
Impedance measurement range
|
0~50kΩ
|
Impedance resolution
|
0.001Ω
|
Short circuit impedance
|
0~100%
|
Working power
|
AC220V±10﹪,50Hz±1Hz
|
Dimensions
|
360mm×220mm×150mm
|
Weight
|
About 5kg (host)
|
Key words
Previous article
NDBRY-III transformer winding deformation tester
NDBYC-2000 Transformer on-load switch tester