Troubleshooting and Handling Methods for Resonant Test Equipment Failures

发布时间:2023-02-14


  The main components of a typical resonant test system used in the power industry include an adjustable-frequency voltage‑regulating power supply, an isolation transformer, a reactor, an excitation transformer, and a capacitive voltage divider. The output of the adjustable-frequency power supply is coupled via the excitation transformer to the series resonant circuit, providing the excitation power required for the resonant test setup. Next, let’s examine the troubleshooting and repair procedures for common faults in resonant test systems.

0d65e796-4b61-46df-aaf4-56a770874901.jpg

  Common precautions for resonant test equipment:

  1. When operating the vibration testing equipment, there must be at least two operators, and the company’s operating procedures must be strictly followed during use.

  2. Test equipment shall be operated by qualified personnel trained in its use. Prior to testing, thorough preparatory procedures must be carried out, including familiarization with the operating manual and repeated hands-on training.

  3. Equipment wiring shall be performed in accordance with applicable standards, and equipment must not be damaged due to incorrect wiring.

  4. To ensure the safety and accuracy of each test, every operator must not only be familiar with the product manual but also follow the operating procedures prescribed by national regulations.

  5. When using this device, the output is high‑voltage or extra‑high‑voltage; ensure reliable grounding during operation and observe safety precautions.

  Causes and troubleshooting methods for common faults in resonant test equipment:

  1. Automatic tuning cannot be completed; no resonance point can be found:

  Phenomenon: The tuning curve is a perfect straight line. After tuning is complete, the instrument indicates that no resonance point has been detected.

  Cause analysis: The circuit grounding is not sufficiently reliable; this may be due to incorrect wiring in the test circuit or an open circuit in the wiring of a particular device.

  Elimination method:

  1. Verify that the grounding equipment is reliable and that the grounding conductor is intact;

  2. Check the continuity of each reactor;

  3. Check the continuity of the high- and low-voltage windings of the vibration test apparatus.

  4. Check the continuity of the high- and low-voltage capacitor arms of the voltage divider.

  5. Check whether the voltage divider signal line is conductive.

  6. If the equipment itself does not exhibit a resonant point during voltage boosting, also check the continuity of the compensation capacitor.

  II. The resonant test apparatus fails to start:

  Cause analysis: After performing fault protection, emergency stop, or detuning protection operations, we failed to press the “Fault Reset” button in a timely manner.

  Elimination method:

  1. First, turn off the device’s power and let it remain off for half an hour. Then, restart the device by pressing the “Reset” button on the device panel, and reboot it once more.

  2. If the fan still does not operate properly, you should contact the manufacturer and refrain from disassembling the unit yourself.

  The above outlines the troubleshooting and repair procedures for resonance test equipment. For more information, please feel free to contact us—our customer service team is available online at any time to assist you! Our company boasts many years of experience in manufacturing resonance test systems and warmly welcomes your inquiry.