undefined

undefined

Product Center


MengziNDLS-6OA SF6 Gas Online Monitoring System

Category:

MengziPartial Discharge-Free Detection and Live On-Line Monitoring Series

Phone: 0512-66101666

Product Description

Technical Features

  • In the environment Science Fiction 6 Gas concentration detection function
  • Environmental oxygen concentration detection function
  • Environmental temperature and humidity monitoring function
  • Real-time display of telemetry and remote signaling data from all monitoring points in the environment.
  • Real-time display of alarm information from all monitoring points in the environment.
  • Setpoint Adjustment Function
  • Science Fiction 6 Gas concentration over-limit and oxygen deficiency alarm functions
  • Hypoxia or Science Fiction 6 Excessive concentration, forced ventilation function
  • Automatic fan start-up upon alarm activation
  • Automatic timed ventilation function
  • Manually force all fans to start or stop. ,
  • Historical data query, display, and storage functions
  • Historical trend query and display function for telemetry values
  • Enter GIS Room automatic broadcast of the current environmental status feature
  • Multi‑monitoring‑point configuration feature for different regions
  • Multi-point networking functionality enables integration with communication protocols and substation backend databases. ( Reserved )
  • Provides a universal communication interface and includes provisions for integration with backend monitoring and fire‑protection systems. ( Reserved )
  • Alarm information storage and recording function
  • Audio-visual and voice alarm functions
  • Remote alarm function
  • Human body infrared detection and sensing function
  • Remote Data Transmission Function

 

1.4  Technical Specifications

  • Operating voltage: AC/DC 220V ± 10%, 50 Hz
  • Power Consumption: Less than under rated voltage 10W
  • Accuracy class: 2.5 level
  • Science Fiction 6 Gas concentration measurement range: 0-3000ppm
  • Science Fiction 6 Concentration Overlimit Alarm Point: 1000ppm (National standard value), accuracy < 5%FS
  • Oxygen content detection range: 0-25%
  • Hypoxia alarm threshold: 18% (National standard value), accuracy < 1%FS
  • Temperature detection range: -30 — +99 °C ( Accuracy ± 0.5 °C )
  • Humidity detection range: 10-99%RH : Accuracy ± 0.5 % Human Resources   
  • Wind turbine output power connection: 6 A ; 
  • Remote communication method: 485/Ethernet
  • On-site host external dimensions (mm) :L330 × W250 × H65
  • Science Fiction 6 and the dimensions of the oxygen detection unit (mm) :L162 × W150 × H38
  • Dimensions of the temperature and humidity sensing unit (mm) :L162 × W150 × H38
  • Monitoring historical data storage capacity: 500 Ten thousand items;
  • Touchscreen size: 7 inch
  • Mounting method for the host and detection unit: wall-mounted.
  • Operating ambient temperature: -25 °C~ 70 °C
  • Operating environment humidity: ≤ 95 %
  • According to GB/T 17626 The regulations and methods for testing the electromagnetic compatibility performance indicators of this device are as follows:

Electrostatic discharge, 4 level

Radio-frequency electromagnetic field immunity, 3 level

Electrical fast transient burst immunity, 4 level

Surge (impulse) immunity, 4 level

Conducted immunity to radio-frequency field-induced disturbances, 3 level

Power-frequency magnetic field immunity, 5 level

Pulse magnetic field immunity, 5 level

Damped oscillatory magnetic field immunity, 5 level

Voltage sag and short-duration interruption immunity, 60%UT , continuous 10 one cycle;

  • According to GB/T 11287 、 GB/T 14573 The regulations and methods for testing the mechanical performance parameters of this device are as follows:

Vibration response, 1 level

Vibration resistance, 1 level

Impact response, 1 level

Impact durability, 1 level

Collision, 1 level

Welcome to leave us an online message; we will get back to you promptly.

%{tishi_zhanwei}%