Product Center
TianshuiNDLS-6OA SF6 Gas Online Monitoring System
Category:
TianshuiPartial Discharge-Free Detection and Live On-Line Monitoring Series
Phone: 0512-66101666
Product Description
Technical Features
- In the environment Science Fiction 6 Gas concentration detection function
- Environmental oxygen concentration detection function
- Environmental temperature and humidity monitoring function
- Real-time display of telemetry and remote signaling data from all monitoring points in the environment.
- Real-time display of alarm information from all monitoring points in the environment.
- Setpoint Adjustment Function
- Science Fiction 6 Gas concentration over-limit and oxygen deficiency alarm functions
- Hypoxia or Science Fiction 6 Excessive concentration, forced ventilation function
- Automatic fan start-up upon alarm activation
- Automatic timed ventilation function
- Manually force all fans to start or stop. ,
- Historical data query, display, and storage functions
- Historical trend query and display function for telemetry values
- Enter GIS Room automatic broadcast of the current environmental status feature
- Multi‑monitoring‑point configuration feature for different regions
- Multi-point networking functionality enables integration with communication protocols and substation backend databases. ( Reserved )
- Provides a universal communication interface and includes provisions for integration with backend monitoring and fire‑protection systems. ( Reserved )
- Alarm information storage and recording function
- Audio-visual and voice alarm functions
- Remote alarm function
- Human body infrared detection and sensing function
- Remote Data Transmission Function
1.4 Technical Specifications
- Operating voltage: AC/DC 220V ± 10%, 50 Hz
- Power Consumption: Less than under rated voltage 10W
- Accuracy class: 2.5 level
- Science Fiction 6 Gas concentration measurement range: 0-3000ppm
- Science Fiction 6 Concentration Overlimit Alarm Point: 1000ppm (National standard value), accuracy < 5%FS
- Oxygen content detection range: 0-25%
- Hypoxia alarm threshold: 18% (National standard value), accuracy < 1%FS
- Temperature detection range: -30 — +99 °C ( Accuracy ± 0.5 °C )
- Humidity detection range: 10-99%RH : Accuracy ± 0.5 % Human Resources
- Wind turbine output power connection: 6 A ;
- Remote communication method: 485/Ethernet
- On-site host external dimensions (mm) :L330 × W250 × H65
- Science Fiction 6 and the dimensions of the oxygen detection unit (mm) :L162 × W150 × H38
- Dimensions of the temperature and humidity sensing unit (mm) :L162 × W150 × H38
- Monitoring historical data storage capacity: 500 Ten thousand items;
- Touchscreen size: 7 inch
- Mounting method for the host and detection unit: wall-mounted.
- Operating ambient temperature: -25 °C~ 70 °C
- Operating environment humidity: ≤ 95 %
- According to GB/T 17626 The regulations and methods for testing the electromagnetic compatibility performance indicators of this device are as follows:
Electrostatic discharge, 4 level
Radio-frequency electromagnetic field immunity, 3 level
Electrical fast transient burst immunity, 4 level
Surge (impulse) immunity, 4 level
Conducted immunity to radio-frequency field-induced disturbances, 3 level
Power-frequency magnetic field immunity, 5 level
Pulse magnetic field immunity, 5 level
Damped oscillatory magnetic field immunity, 5 level
Voltage sag and short-duration interruption immunity, 60%UT , continuous 10 one cycle;
- According to GB/T 11287 、 GB/T 14573 The regulations and methods for testing the mechanical performance parameters of this device are as follows:
Vibration response, 1 level
Vibration resistance, 1 level
Impact response, 1 level
Impact durability, 1 level
Collision, 1 level
Contact Us
National Service Hotline: 400-027-8938
Mobile (Manager Chen): 133 9714 9829
Address: Building No. 5, Donghu High-tech Industrial Innovation Base, No. 9 Miaoshan Avenue, Miaoshan Development Zone, Jiangxia District, Wuhan City
Scan it
Follow the official mobile website