Copyright:Wuhan Southstar Electric Power Technology Co., Ltd. 鄂ICP备06008607号 Website:300.cn Wuhan
Back to top
Chuangzhi Tiandi, No.13 Yangqiaohu
Avenue, Zanglong Island, Wuhan
Nanxing Power APP
Mailbox:whnx999@126.com
Telephone:400-027-8938
Southstar Electric Power Technology Co., Ltd.
About us
Sales service
News
Recruitment
Contact us
Product display
Wuhan Southstar Electric Power Technology
Co., Ltd. I sincerely look forward to Work
hard with you to create a better future!
Page view:
产品名称
NDBYC-2000 Transformer on-load switch tester
Affiliate classification
Transformer detection class
Quantity
-
+
Product description
Product parameters
Reference standard: GB/T 10584-1989, DL/T846.8-2004.
Features:
● Test Y0, Y, △ type transformer, the resistance value is directly displayed without conversion;
● Humanized data analysis can automatically find faults in the middle of the waveform and make marks;
● The display of the waveform is automatically adjusted according to the data returned from the sample and the amplitude of the time;
● It can be tested with or without windings;
● Four-terminal wiring method, providing high-precision resistance measurement without wire compensation;
● Continuous testing can be carried out in the middle of the test to save time for transformer power failure.
The main parameters:
Three-phase constant current source
|
1A File; 0.2A File
|
|
Port maximum voltage
|
24V
|
|
Transition resistance measurement range
|
1A File:0.8Ω~20Ω
|
Resolution: 0.1Ω,
Accuracy: ±5% Reading ±0.1Ω
|
0.2A File:10Ω~100Ω
|
||
Transition time measurement range
|
Sampling rate: 20k, resolution: 0.1ms, accuracy: ±1% reading ±0.2mS
|
|
Waveform recording time length
|
300ms
|
|
Dimensions
|
410mm×320mm×200mm
|
|
Weight
|
About 8kg
|
Key words
Previous article
NDBRY-II Transformer low voltage impedance short circuit tester
NDR series DC resistance tester
Next article